Grease Trap Sizing Guide for Florida Restaurants
The right grease trap or interceptor size depends on three factors: your fixture flow rate, your menu type, and your local Florida building code requirements. An undersized unit will overflow, fail inspections, and potentially cause sewer backups. An oversized unit wastes money on installation and may still require the same pump-out frequency. Getting it right the first time saves thousands of dollars over the life of your equipment.
For most Florida restaurants, you'll need either an interior grease trap rated at 20-100 GPM or an underground grease interceptor with 500 to 2,000 gallons capacity.
Understanding PDI Sizing Standards
The Plumbing & Drainage Institute (PDI) sets the industry standards for grease trap sizing. Two standards apply:
PDI-G101 — Gravity Grease Interceptors (passive traps)
- Rates traps by flow rate in gallons per minute (GPM)
- Standard sizes: 10, 15, 20, 25, 35, 50, 75, and 100 GPM
- Used for indoor, point-of-use installations
PDI-G102 — Automatic Grease Removal Devices (AGRD)
- Self-cleaning units that automatically skim grease
- Higher cost but lower manual maintenance
- Must still meet flow rate requirements
For underground interceptors, the relevant standard is ASME A112.14.3, which sizes units by liquid capacity in gallons.
How to Calculate Your Required Flow Rate
The basic formula for sizing a grease trap uses the fixtures connected to it:
Step 1: List All Connected Fixtures
Identify every plumbing fixture that drains through the grease trap:
- 3-compartment sinks
- Pre-rinse sinks
- Dishwashers (commercial)
- Mop sinks
- Floor drains in cooking areas
- Wok stations
- Prep sinks
Step 2: Determine Fixture Flow Rates
Each fixture type has a standard drainage fixture unit (DFU) rating:
| Fixture | DFU Value | Approx. GPM |
|---|---|---|
| 3-compartment sink | 4 per compartment | 15-20 GPM |
| Pre-rinse sink | 3 | 10-15 GPM |
| Commercial dishwasher | 4-6 | 15-25 GPM |
| Mop sink | 3 | 10-15 GPM |
| Floor drain (2") | 2 | 5-10 GPM |
| Floor drain (3") | 3 | 10-15 GPM |
| Wok station | 3-4 | 10-15 GPM |
Step 3: Calculate Total Flow Rate
Add the GPM values for all fixtures that will drain simultaneously during peak operations. This is your minimum trap size.
Example calculation:
- 1 three-compartment sink: 20 GPM
- 1 pre-rinse sink: 15 GPM
- 1 commercial dishwasher: 20 GPM
- 2 floor drains (2"): 10 GPM each = 20 GPM
- Total: 75 GPM
This kitchen needs at minimum a 75 GPM grease trap or an underground interceptor.
Step 4: Apply Menu Adjustment Factor
Heavy FOG menus require upsizing:
- Light FOG (sandwich shop, bakery, coffee shop): Use calculated size
- Medium FOG (casual dining, pizza, Mexican food): Multiply by 1.25
- Heavy FOG (fried chicken, Chinese, fish fry, deep-fry heavy): Multiply by 1.5
Using our example with a heavy-fry menu: 75 GPM x 1.5 = 112.5 GPM — you need an underground interceptor.
Interior Grease Trap Sizes (20-100 GPM)
Interior grease traps are point-of-use devices installed under sinks or on the floor. Standard sizes available:
| GPM Rating | Grease Capacity | Typical Use |
|---|---|---|
| 20 GPM | 40 lbs | Single sink, coffee shop, small deli |
| 25 GPM | 50 lbs | Small restaurant, 1-2 connected fixtures |
| 35 GPM | 70 lbs | Medium kitchen, 2-3 fixtures |
| 50 GPM | 100 lbs | Larger kitchen, 3-4 fixtures |
| 75 GPM | 150 lbs | High-volume kitchen, multiple fixtures |
| 100 GPM | 200 lbs | Maximum interior size, heavy use |
Interior trap limitations:
- Maximum practical size is 100 GPM — above this, an underground interceptor is required
- Must be cleaned frequently (weekly to biweekly)
- Some Florida counties do not accept interior traps for full-service restaurants regardless of size
Underground Interceptor Sizes (500-2,000+ Gallons)
Underground grease interceptors are required for most full-service Florida restaurants. Standard sizes:
| Capacity | Flow Rate | Typical Use |
|---|---|---|
| 500 gallon | 35-50 GPM | Small restaurant, limited frying |
| 750 gallon | 50-75 GPM | Medium restaurant, moderate menu |
| 1,000 gallon | 75-100 GPM | Full-service restaurant, standard menu |
| 1,500 gallon | 100-150 GPM | High-volume restaurant, heavy frying |
| 2,000 gallon | 150-200 GPM | Large banquet hall, hotel kitchen, hospital |
| 2,000+ gallon | 200+ GPM | Multiple kitchens, food court, institutional |
Key considerations:
- Larger interceptors cost more to install but may reduce pump-out frequency
- The "25% rule" means a 1,000-gallon interceptor needs service when FOG reaches 250 gallons
- Service costs scale with size — a 2,000-gallon pump-out costs more than a 500-gallon one
When You Need to Upgrade
Signs that your current grease trap or interceptor is undersized:
- Frequent pump-outs needed (more often than your county's minimum requirement)
- Repeated FOG inspection failures for exceeding 25% capacity
- Slow drains even shortly after pump-out service
- Menu changes — adding a fryer or expanding kitchen capacity increases FOG load
- Increased business volume — more covers means more FOG
- Grease visible in drain lines downstream of the trap
If you experience any of these, consult a licensed plumber or engineer to evaluate whether you need a larger unit. Contact a grease trap service company in your area — many offer sizing consultations.
Florida Building Code Requirements
The Florida Building Code (FBC) aligns with the International Plumbing Code (IPC) with Florida-specific amendments. Key sizing requirements:
- All commercial food service establishments must have grease removal equipment
- Sizing must follow PDI-G101 (interior traps) or ASME A112.14.3 (underground interceptors)
- Local authority (county/city building department) has final approval on sizing
- Permits required for installation of any grease removal equipment
- Professional installation — must be installed by a licensed plumber
- Inspection required before system goes into service
Additionally, your county's FOG program may have requirements that exceed the state building code. Check with your county's environmental services department.
Common Sizing Mistakes
Mistake 1: Sizing only for current fixtures Plan for your full kitchen buildout, not just what's installed today. Adding a dishwasher or fryer later means your trap is suddenly undersized.
Mistake 2: Ignoring the menu factor A 50 GPM trap might handle the flow from a salad-focused restaurant, but the same fixtures in a fried chicken restaurant need 75 GPM due to higher FOG output.
Mistake 3: Choosing the cheapest option A $300 undersized trap that overflows monthly costs far more than a $1,500 properly sized unit that runs cleanly between quarterly service appointments.
Mistake 4: Not consulting local code Florida has 67 counties with varying FOG requirements. What works in one county may not meet code in another. Always confirm with your local building department before purchasing.
Mistake 5: DIY sizing without professional input While this guide provides general guidance, your final sizing should be confirmed by a licensed plumber or engineer who can evaluate your specific fixtures, layout, and local requirements.
Frequently Asked Questions
Can I install a grease trap myself? No. Florida building code requires a licensed plumber for grease trap and interceptor installation. A permit and inspection are also required. DIY installation voids warranties and can result in code violations.
How much does grease trap installation cost in Florida? Interior traps: $500-$2,000 installed. Underground interceptors: $5,000-$25,000 installed (including excavation). Costs vary by size, location, soil conditions, and local permitting fees. Get quotes from multiple service providers. See our grease trap vs interceptor comparison for a detailed cost breakdown.
Do food trucks need grease traps in Florida? Most Florida counties require food trucks to have portable grease traps (typically 20-40 GPM). Requirements vary by county and commissary arrangements. Check with your county health department and the commissary where you service your truck.
What happens if my grease trap is too big? An oversized trap won't cause code violations, but it increases installation cost and may not function optimally. Grease traps work best when the flow rate matches the rated capacity. An oversized trap with low flow may not achieve proper separation, and you still pay for pump-outs based on tank size, not waste volume.
Frequently Asked Questions
Can I install a grease trap myself?
No. Florida building code requires a licensed plumber for grease trap and interceptor installation. A permit and inspection are also required. DIY installation voids warranties and can result in code violations. **How much does grease trap installation cost in Florida?** Interior traps: $500-$2,000 installed. Underground interceptors: $5,000-$25,000 installed (including excavation). Costs vary by size, location, soil conditions, and local permitting fees. Get quotes from multiple [service providers](/companies). See our [grease trap vs interceptor comparison](/guides/grease-trap-vs-grease-interceptor) for a detailed cost breakdown. **Do food trucks need grease traps in Florida?** Most Florida counties require food trucks to have portable grease traps (typically 20-40 GPM). Requirements vary by county and commissary arrangements. Check with your county health department and the commissary where you service your truck. **What happens if my grease trap is too big?** An oversized trap won't cause code violations, but it increases installation cost and may not function optimally. Grease traps work best when the flow rate matches the rated capacity. An oversized trap with low flow may not achieve proper separation, and you still pay for pump-outs based on tank size, not waste volume.
